Carrier AQUAZONE PSV User Manual

Page 33

background image

33

Heating/Cooling Thermostat Type — Switch 3 provides se-

lection of thermostat type. Heat pump or heat/cool thermostats

can be selected. Select OFF for heat/cool thermostats. When in

heat/cool mode, Y1 is used for cooling stage 1, Y2 is used for

cooling stage 2, W1 is used for heating stage 1 and O/W2 is

used for heating stage 2. Select ON for heat pump thermostats.

In heat pump mode, Y1 used is for compressor stage 1, Y2 is

used for compressor stage 2, W1 is used for heating stage 3 or

emergency heat, and O/W2 is used for reversing valve (heating

or cooling) depending upon switch 4 setting.
O/B Thermostat Type — Switch 4 provides selection for heat

pump O/B thermostats. O is cooling output. B is heating out-

put. Select ON for thermostats with O output. Select OFF for

thermostats with B output.
Dehumidification Fan Mode — Switch 5 provides selection

of normal or dehumidification fan mode. Select OFF for dehu-

midification mode. The fan speed relay will remain OFF dur-

ing cooling stage 2. Select ON for normal mode. The fan speed

relay will turn on during cooling stage 2 in normal mode.
Output — Switch 6 provides selection for DDC operation. If

set to DDC output at EH2, the EH2 terminal will continuously

output the last fault code of the controller. If the control is set to

EH2 normal, then the EH2 will operate as standard electric

heat output. Set the switch to ON to set the EH2 to normal. Set

the switch to OFF to set the DDC output at EH2.
Boilerless Operation — Switch 7 provides selection of boiler-

less operation and works in conjunction with switch 8. In boil-

erless operation mode, only the compressor is used for heating

when FP1 is above the boilerless changeover temperature set

by switch 8 below. Select ON for normal operation or select

OFF for boilerless operation.
Boilerless Changeover Temperature — Switch 8 on S1 pro-

vides selection of boilerless changeover temperature set point.

Select OFF for set point of 50 F or select ON for set point of

40 F.

If switch 8 is set for 50 F, then the compressor will be used

for heating as long as the FP1 is above 50 F. The compressor

will not be used for heating when the FP1 is below 50 F and the

compressor will operates in emergency heat mode, staging on

EH1 and EH2 to provide heat. If a thermal switch is being used

instead of the FP1 thermistor, only the compressor will be used

for heating mode when the FP1 terminals are closed. If the FP1

terminals are open, the compressor is not used and the control

goes into emergency heat mode.
DIP SWITCH BANK 2 (S2) — This set of DIP switches is

used to configure accessory relay options.
Switches 1 to 3 — These DIP switches provide selection of

Accessory 1 relay options. See Table 14 for DIP switch

combinations.
Switches 4 to 6 — These DIP switches provide selection of

Accessory 2 relay options. See Table 15 for DIP switch

combinations.

Table 14 — DIP Switch Block S2 —

Accessory 1 Relay Options

LEGEND

NOTE: All other DIP switch combinations are invalid.

Table 15 — DIP Switch Block S2 —

Accessory 2 Relay Options

LEGEND

NOTE: All other switch combinations are invalid.

Auto Dehumidification Mode or High Fan Mode — Switch 7

provides selection of auto dehumidification fan mode or high

fan mode. In auto dehumidification fan mode, the fan speed

relay will remain off during cooling stage 2 if terminal H is

active. In high fan mode, the fan enable and fan speed relays will

turn on when terminal H is active. Set the switch to ON for auto

dehumidification fan mode or to OFF for high fan mode.
Factory Setting — Switch 8 is set to ON. Do not change the

switch to OFF unless instructed to do so by the factory.

Units with Modulating Hot Water Reheat
(HWR) Option —

A heat pump equipped with hot water

reheat (HWR) can operate in three modes: cooling, cooling

with reheat, and heating. The cooling and heating modes are

like any other water source heat pump. The reversing valve

("O" signal) is energized in cooling, along with the compressor

contactor(s) and blower relay. In the heating mode, the revers-

ing valve is deenergized. Almost any thermostat will activate

the heat pump in heating or cooling modes. The Deluxe D

microprocessor board, which is standard with the HWR

option, will accept either heat pump (Y,O) thermostats or non-

heat pump (Y,W) thermostats.

The reheat mode requires either a separate humidistat/

dehumidistat or a thermostat that has an integrated dehumidifi-

cation function for activation. The Deluxe D board is config-

ured to work with either a humidistat or dehumidistat input to

terminal “H” (DIP switch settings for the Deluxe D board are

shown in Table 16). Upon receiving an “H” input, the Deluxe

D board will activate the cooling mode and engage reheat.

Table 16 — Humidistat/Dehumidistat Logic and

Deluxe D DIP Switch Settings

Table 17 shows the relationship between thermostat input

signals and unit operation. There are four operational inputs for

single-stage units and six operational inputs for dual-stage

units:
• Fan Only

• Cooling Stage 1

• Cooling Stage 2

• Heating Stage 1

• Heating Stage 2

• Reheat Mode

ACCESSORY 1

RELAY OPTIONS

DIP SWITCH POSITION

1

2

3

Cycle with Fan

On

On

On

Digital NSB

Off

On

On

Water Valve — Slow Opening

On

Off

On

OAD

On

On

Off

Reheat — Humidistat

Off

Off

Off

Reheat — Dehumidistat

Off

On

Off

NSB — Night Setback
OAD — Outside Air Damper

ACCESSORY 2

RELAY OPTIONS

DIP SWITCH POSITION

4

5

6

Cycle with Compressor

On

On

On

Digital NSB

Off

On

On

Water Valve — Slow Opening

On

Off

On

OAD

On

On

Off

NSB — Night Setback
OAD — Outside Air Damper

Sensor

2.1

2.2

2.3

Logic

Reheat

(ON) - H

Reheat

(OFF) - H

Humidistat

Off

Off

Off

Reverse

0 VAC

24 VAC

Dehumidistat

Off

On

Off

Standard

24 VAC

0 VAC