667 Schd (Schedule) Menu (1 of 1)
Item Field
Description
Range
Access
Level
LT
D
USERINS
T
AD
V
Override The setback override that is in effect for the snow
melting system.
NONE, AWAY (Ovr)
Default = NONE
667 Misc (Miscellaneous) Menu (1 of 1)
Item Field
Description
Range
Access
Level
LT
D
USERINS
T
AD
V
Units The units of measure that all of the temperatures are to be
displayed in by the control.
°F, °C
Default = °F
Backlite The operating mode for the back lighting on the LCD
as well as time of keypad inactivity until the control automatically
returns to the default display.
OFF, 30 sec, ON
Default = ON
Access The access level that is to be used by the control.
DIP switch = Unlock
ADV, INST, USER,
LTD
Default = INST
Non-Cop The number of times that the control has been
powered up since this item was last cleared. This number will
increase if there is a lowering of the input voltage beyond the
control’s usable range. This item can be used as an indication
of the quality of the power source.
0 to 255
tN2 Communication The number of times that a communication
error has been detected between the control and either an RDM
or Remote Start / Stop Module since this item was last cleared.
If the wires between the control and the tekmar Net™ tN2
device are run in a noisy electrical environment, this can cause
interference in the communication between the control and the
tN2 device.
0 to 255
667 Monitor Menu (3 of 3)
Item Field
Description
Range
Access
Level
LT
D
USERINS
T