tekmar 667 Snow Detector & Melting Control Installation User Manual

Page 24

background image

24 of 32

©

2009 D

667

-

03/09

667 Schd (Schedule) Menu (1 of 1)

Item Field

Description

Range

Access

Level

LT

D

USERINS

T

AD

V

Override The setback override that is in effect for the snow
melting system.

NONE, AWAY (Ovr)

Default = NONE

667 Misc (Miscellaneous) Menu (1 of 1)

Item Field

Description

Range

Access

Level

LT

D

USERINS

T

AD

V

Units The units of measure that all of the temperatures are to be
displayed in by the control.

°F, °C
Default = °F

Backlite The operating mode for the back lighting on the LCD
as well as time of keypad inactivity until the control automatically
returns to the default display.

OFF, 30 sec, ON
Default = ON

Access The access level that is to be used by the control.
DIP switch = Unlock

ADV, INST, USER,
LTD
Default = INST

Non-Cop The number of times that the control has been
powered up since this item was last cleared. This number will
increase if there is a lowering of the input voltage beyond the
control’s usable range. This item can be used as an indication
of the quality of the power source.

0 to 255

tN2 Communication The number of times that a communication
error has been detected between the control and either an RDM
or Remote Start / Stop Module since this item was last cleared.
If the wires between the control and the tekmar Net™ tN2
device are run in a noisy electrical environment, this can cause
interference in the communication between the control and the
tN2 device.

0 to 255

667 Monitor Menu (3 of 3)

Item Field

Description

Range

Access

Level

LT

D

USERINS

T

AD

V