tekmar 667 Snow Detector & Melting Control Installation User Manual

Page 21

background image

21 of 32

©

2009 D

667

-

03/09

Item Field

Access

Level

Description

Range

Actual

Setting

Section

LT

D

USERINS

T

AD

V

667 Adjust Menu (1 of 2)

B1

Run Time The time for which a zone is operated
once it has reached its melting temperature.
This item cannot be viewed if a Remote
Start / Stop Module 039 has been connected.

0:30 to 17:00 hr,
INF (Infi nity)
Default = 4:00 hr

E1

Add Melt The additional time for which a zone
is operated once the Snow / Ice Sensor 090
becomes dry.
090 is present

0:00 to 6:00 hr
Default = 0:30 hr

D1

Sensitivity Sensitivity of water detection of the
Snow / Ice Sensor 090.
090 is present

AUTO, 20 to 80%
Default = AUTO

E1

Melting The desired slab surface temperature
while in the Melting mode.

32 to 95°F
(0 to 35°C)
Default = 36°F (2°C)

F1

Idling The desired slab surface temperature of
the Idling mode.

OFF, 20 to 95°F
(OFF, -7 to 35°C)
Default = OFF

A

Temporary Idle Time for which the temporary
idle is active.

OFF, 0:30 to 40:00 hr
Default = OFF

B

WWSD Warm Weather Shut Down. Slab must
exceed 34°F to enter WWSD.

AUTO, 32 to 95°F
(AUTO, 0 to 36°C)
Default = AUTO

B1

CWCO The Cold Weather Cut Out temperature
for the snow melting system.

OFF, -30 to 50°F
(OFF, -34 to 10°C)
Default = 10°F (-12°C)

A

Mix Maximum The maximum supply water
temperature for the mixing system.

80 to 210°F, OFF
(27 to 99°C, OFF)
Default = 150°F (66°C)

C

Boiler Sensor The location of the boiler sensor.
This affects operation of the Boiler contact.

SUP, RET, NONE
Default = SUP

B1

ΔT Maximum The maximum ΔT for the snow
melting system.

10 to 70°F, OFF
(5 to 39°C, OFF)
Default = OFF