Differential The differential for the snow
melting system.
Boil SENS = SUP

AUTO, 2 to 42°F
(AUTO, 1 to 23°C)
Default = AUTO

A

C1

Boiler Minimum The minimum temperature
allowed for the boiler target temperature.
Boil SENS ≠ NONE

OFF, 80 to 180°F
(OFF, 27 to 82°C)
Default = 140° (60°C)

C1

Fire Delay The time delay the control can expect
between the time the Boiler contact closes and
the boiler fi res.
Boil SENS = SUP

0:00 to 3:00 minutes
Default = 0:10 min

C1

Boiler Mass The thermal mass characteristics of
the boiler that is being used.
Boil SENS = SUP

LITE, MED, HEVY
Default = MED

A

Exercise The frequency with which the control
exercises the pumps and valves that are operated
by the control.

30 to 240 hours,
(in 10 hour steps)
Default = 70 hr

Item Field

Access

Level

Description

Range

Actual

Setting

Section

LT

D

USERINS

T

AD

V

667 Adjust Menu (2 of 2)

667 Monitor Menu (1 of 3)

Outdoor High The highest recorded outdoor air temperature
since this item was last cleared.

-67 to 149°F
(-55 to 65°C)

Outdoor Low The lowest recorded outdoor air temperature
since this item was last cleared.

-67 to 149°F
(-55 to 65°C)

Slab High The highest recorded temperature at the slab sensor
since this item was last cleared.

-58 to 167°F
(-50 to 75°C)

Item Field

Description

Range

Access

Level

LT

D

USERINS

T

AD

V