tekmar 665 Snow Detector & Melting Control Installation User Manual

Data brochure, D 665, Snow detector & melting control 665

background image

1

of

28

©

2012 D

665

-

04/12

- Data Brochure

Snow Detector & Melting Control 665

D 665

04/12

Replaces: 12/08

The Snow Detector & Melting Control 665 is a microprocessor-based control which operates a single zone snow melting system.
The control can operate automatically when a Snow / Ice Sensor 090 is installed or the user can manually enable and/or disable the
system. When the control is in the melting mode, the slab is maintained at a “Melting” temperature through an on/off output which
operates a contactor for electrical cables, a boiler, an injection pump or an injection valve. When the control is not in the melting mode,
the melt system can either be shut down or it can be maintained at an idle temperature for faster response and improved safety. The
665 control includes a large Liquid Crystal Display (LCD) in order to view system status and operating information.

Additional features include:

1

Red

2

Blk

3

Blu

4

Yel

5

Brn/
Slab

6

Out

7

Com

8

tN2

9

Melt/Idle
Demand

10 11

Heat

12

13

Melting

14

15

17

Sys

P1

16

Power

L

N

Test

Snow Detector & Melting Control 665

Pulse Width Modulation

Idle Demand

Melt Demand

not testing

testing

testing paused

For maximum heat,
press and hold Test
button for 3 seconds.

off

red

red

Do not apply power

Input

Snow/Ice Sensor

090 installed with

Sensor Socket

091 Optional

Input

Slab Sensor

Optional

Input

Remote Display Module (RDM)

or

Remote Start / Stop Module

or

Input

Outdoor

Sensor

Included

Input

Melt/Idle
Demand

Output
System
Pump

Input
115 V (ac)
Power
Supply

OR

Melt Demand

Idle Demand

WWSD

Water

Melting

Start

Menu

Item

Stop

Do not apply power

Output

Boiler

Output

Turn on injection

pump

Output

Turn on relay for

electric cables

Output
Melt Relay

OR

OR

Signal wiring must be rated at least 300 V.

900-03
Designed and assembled in Canada by
tekmar Control Systems Ltd.

Power

115 V ± 10% 50/60 Hz 600 VA

Relays

230 V (ac) 5 A 1/3 hp

Demand

20 to 260 V (ac) 2 VA

Meets Class B:
Canadian ICES
FCC Part 15

H2028D

Dat

e Code

• Slab

Outdoor

Reset

Automatic snow detection and melt control (with 090 sensor)

• Temporary

Idle

• Manual

Override

Warm Weather Shut Down

Cold Weather Cut Out

Remote display and adjustment capabilities

Test sequence to ensure proper component operation

• Equipment

Exercising

CSA C US certifi ed (approved to applicable UL standards)