View menu, Adjus t menu – tekmar 545 Thermostat Installation User Manual
Page 6

© 2008
D 545 - 07/08
6 of 40
Item Field
Range
Access
Description
-58 to 212°F
(-50.0 to 100.0°C)
INST
ADV
DUCT SENSOR
SECTION
A
Current temperature at the duct sensor.
Note: This item is only available when Sensor 2 is
set to Duct.
-22 to 266°F
(-30.0 to 130.0°C)
INST
ADV
SUPPLY TEMPERATURE OF TN4 BUS
SECTION F
Actual water temperature of the tN4 bus for the first
stage of heat.
Note: This item is only available when the thermostat
is connected to an Outdoor Reset Module and the
DIP switch is set to tN4 System Control.
View Menu (2 of 2)
After the last item, the control returns to the first item in the menu.
VIEW MENU
Item Field
Range
Access
Description
YES, NO
Default = NO
USER
INST
ADV
CLEAR FILTER
SECTION J
Indicates when to reset the air filter timer.
Note: This item is only available when Filter is set to
ON, the air filter timer has expired and the Fan Mode
is set to 1 or 2.
OFF, HEAT,
AUTO, COOL
Default = AUTO
USER
INST
ADV
MODE OF OPERATION
SECTION B
Mode of operation of the thermostat or cool group.
40 to 95°F
(4.5 to 35.0°C)
LTD
USER
INST
ADV
SET HEAT
SECTION C
Selected air heating temperature for each event.
Note: At the Limited Access Level, you can only
adjust the temperature +/-3°F (1.5°C) from the last
setting.
Away is only available when Scenes are turned on.
Wake
Default = 70°F (21.0°C)
UnOccupied
Default = 62°F (16.5°C)
Occupied
Default = 70°F (21.0°C)
Sleep
Default = 62°F (16.5°C)
Away
Default = 62°F (16.5°C)
Adjust Menu (1 of 7)
The Adjust Menu items are the programmable settings
used to operate the mechanical equipment.
Continued on next page.
ADJUS
T MENU