Misc menu – tekmar 545 Thermostat Installation User Manual
Page 22

© 2008
D 545 - 07/08
22 of 40
Item Field
Range
Access
Description
SEC, LTD, USER,
INST, ADV
Default = USER
SEC
LTD
USER
INST
ADV
ACCESS LEVEL
The access level of the thermostat. The access column
shows which items are visible in each access level.
Note: This item is only available when the Lock /
Unlock DIP switch on the thermostat and the tN4
system control are set to Unlock.
°F, °C
Default = °F
USER
INST
ADV
UNITS
SECTION
T
Select Fahrenheit or Celsius as the temperature
units.
ON, TMPY, OFF
Default = TMPY
USER
INST
ADV
BACKLIGHT
SECTION
U
Select whether the backlight displays permanently,
temporarily, or is off. The temporary backlight lasts
for 30 seconds.
-5.0 to +5.0°F in
0.1°F increments
(-3.0° to +3.0°C in
0.1°C increments)
Default = 0.0°F
ADV
OFFSET
SECTION
Q
Fine tune the current room temperature. Adjustments
are in tenths of a degree.
– – –, -bus#:01,
... bus#:24, DEF
Default = – – –
INST
ADV
COPY SETTINGS
SECTION
V
Copy settings from another thermostat to this
thermostat.
1. Select the address of the thermostat to copy from.
Select DEF to load the factory default settings.
2. Wait for 3 seconds and then press the Up and Down
buttons for 1 second.
3. The thermostat will show the percentage of progress.
4. Displays DONE if successful or WARN if only part
of the settings were copied.
Misc (Miscellaneous) Menu (1 of 2)
The Miscellaneous menu items set display and control
options such as access level and temperature units.
Continued on next page.
MISC MENU