Temperature vs. Resistance Table - Continued

Temperature

Resistance

°F

°C

100

38

5,828

105

41

5,210

110

43

4,665

115

46

4,184

120

49

3,760

125

52

3,383

130

54

3,050

135

57

2,754

140

60

2,490

145

63

2,255

150

66

2,045

155

68

1,857

160

71

1,689

Temperature

Resistance

°F

°C

165

74

1,538

170

77

1,403

175

79

1,281

180

82

1,172

185

85

1,073

190

88

983

195

91

903

200

93

829

205

96

763

210

99

703

215

102

648

220

104

598

225

107

553

Thermostat Wiring

Zone Valve

---------------------------------------------------------

---------------------------------------------------------

C

N

L

R

C

R

Y/W2 Rc

G

G

Rh W1

S1 S2

Com

No Power

T

T

Zone
Valve

Boiler

Transformer

Field Jumper Required:
R to Rh