Technical data, Frequently asked questions – tekmar 521 Programmable Thermostat Installation User Manual
Page 27
© 2014
521_D - 01/14
27 of 28
A Watts Water Technologies Company
Technical Data
Programmable Thermostat 521 Two Heat or Heat-Cool (Includes Sensor 079)
Literature
521_A, 521_C, 521_D, 521_Q, 521_U
Control
Microprocessor control. This is not a safety (limit) control
Packaged weight
0.6 lb. (290 g)
Dimensions
3-11/16” H x 3” W x 15/16” D (94 x 76 x 24 mm)
Enclosure
White PVC plastic, NEMA type 1
Approvals
Meets Class B: ICES & FCC Part 15, CE
Ambient conditions
Indoor use only, 32 to 122°F (0 to 50°C), RH ≤90% non-condensing
Power supply
10 to 30 V (ac/dc), 50/60 Hz, 1.8 VA, Class 2
Relay
30 V (ac/dc) 2 A, Class 2 circuits
Sensor
NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892
– Included
Slab Sensor 079
– Optional
tekmar type # 070, 072, 073, 076, 077, 079, 084
Frequently Asked Questions
Symptom
Look for...
Corrective Action
Display powering
on and off.
Measure voltage at
wiring terminals R
and C.
The power supply transformer
may have limited VA capacity. A
transformer with a larger VA rating is
recommended.
Heat not on
Mode Off or Cool
Thermostat must be in Mode Heat in
order to provide heating.
Floor Max
The floor has reached the maximum
operating temperature.
Room is too
hot due to floor
heating being on
Floor Min
Lower the Set Floor temperature
setting.
Cooling not on
Mode Off or Heat
Thermostat must be in Mode Cool in
order to provide cooling.
Slab Sensor 079 10’ (3 m) wire
Dimensions
3/16” OD x 1-1/2” (5 mm OD x 38 mm)
Enclosure
316 stainless steel, 10’ (3 m) 24 AWG, 300 volt PVC insulated Zipcord
Approvals
CSA C US
Operating range
-58 to 221°F (-50 to 105°C)
Sensor
NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) Я=3892