Misc. menus – tekmar 364 Universal Reset Control Installation User Manual

Page 29

background image

29 of 36

© 2001

D 364 - 07/01

Item Field

Access
Level

Description

Range

Actual

Setting

Section

LT

D

USER

INS

T

AD

V

364 Adjust Menu (5 of 5)

364 Misc (Miscellaneous) Menu (1 of 1)

Item Field

Description

Range

Access
Level

LT

D

USER

INS

T

AD

V

OFF, 30 sec, ON
Default = ON

ADV, INST, USER,
LTD
Default = INST

The frequency with which the control will exer-
cise the pumps and valves that are operated by
the control.

The units of measure that all of the temperatures are to be
displayed in by the control.

The operating mode for the back lighting on the LCD as well
as the time of keypad inactivity until the control automatically
returns to the default display.
BACKLITE = OFF (returns after 10 seconds),
BACKLITE = 30 sec (returns after 30 seconds),
BACKLITE = ON (returns after 90 seconds)

The access level that is to be used by the control.
DIP switch Unlock

30 to 240 hr
Default = 70 hr

°F, °C
Default = °F