364 Adjust Menu (2 of 5)

Item Field

Access
Level

Description

Range

Actual

Setting

Section

LT

D

USER

INS

T

AD

V

OFF, -30 to 50°F
(OFF, -34 to 10°C)
Default = 10°F (-12°C)

E1

35 to 100°F
(2 to 38°C)
Default = 70°F (21°C)

D1

NONE, INDR,
ZOIN, SLAB (only
if MIX MIN = OFF)
Default = NONE

D3

NONE, SLAB
Default = NONE

E2
E3

OFF, 35 to 120°F
(OFF, 2 to 49°C)
Default = 70°F (21°C)

D3

40 to 150°F
(4 to 66°C)
Default = 90°F (32°C)

D3

HRF1, HRF2, COIL,
CONV, RAD, BASE
Default = HRF1

A

OFF, 35 to 150°F
(OFF, 2 to 66°C)
Default = OFF

D1

35 to 100°F
(2 to 38°C)
Default = 70°F (21°C)

D1

70 to 220°F
(21 to 104°C)
Default = 120°F (49°C)

D1

The maximum

∆T for the snow melting slab.

DIP switch = Snow Melting

The Cold Weather Cut Off temperature for the
snow melting system.
DIP switch = Snow Melting

The desired room air temperature for the mixing
zones. Note: There is only a ±3°F (±1°C) adjust-
ment in the LTD access level.
DIP switch = Mixing Reset

The device that is connected to the Mix 10K
input.
DIP switch = Mixing Reset

Selects if a slab sensor is connected to the
control.
DIP switch = Snow Melting

The minimum temperature at the slab sensor
as long as the control is not in WWSD.
DIP switch = Mixing Reset, MIX 10K = SLAB

The maximum temperature at the slab sensor.
DIP switch = Mixing Reset, MIX 10K = SLAB

The type of terminal units that are being used
for the mixing side of the heating system.
DIP switch = Mixing Reset

The minimum supply water temperature for the
mixing system.
DIP switch = Mixing Reset

The design indoor air temperature used in the
heat loss calculation for the mixing system.
DIP switch = Mixing Reset

The design supply temperature used in the heat
loss calculation for the mixing system.
DIP switch = Mixing Reset

10 to 70°F, OFF
(-6 to 39°C, OFF)
Default = 40°F (22°C)

E1