tekmar 364 Universal Reset Control Installation User Manual

Page 27

background image

27 of 36

© 2001

D 364 - 07/01

Item Field

Access
Level

Description

Range

Actual

Setting

Section

LT

D

USER

INS

T

AD

V

364 Adjust Menu (3 of 5)

-60 to 50°F
(-51 to 10°C)
Default = 10°F (-12°C)

B1
D1

FLOT (Floating),
VAR (Variable Speed)
Default = VAR

D2

30 to 230 sec
Default = 160 sec

D2

SUP (Supply), RET
(Return), NONE
Default = SUP

F

35 to 100°F
(2 to 38°C)
Default = 70°F (21°C)

B1

HRF1, HRF2,
COIL, CONV,
RAD, BASE
Default = CONV

A

35 to 100°F
(2 to 38°C)
Default = 70°F (21°C)

B1

70 to 220°F
(21 to 104°C)
Default = 190°F (88°C)

B1

120 to 225°F, OFF
(49 to 107°C, OFF)
Default = 210°F (99°C)

B1

F1

OFF, 80 to 180°F
(OFF, 27 to 82°C)
Default = 140°F (60°C)

B1

F1

The maximum supply temperature for the
mixing system.

The design outdoor air temperature used in the
heat loss calculation for the heating system.

The type of mixing device that is to be used in
the heating system.

The time that the actuating motor requires to
operate from fully closed to fully open.
MIXING = FLOT

The location for the boiler sensor. This affects
operation of the boiler contact.

The desired room air temperature for the boiler
zones. Note: There is only a ±3°F (±1°C) adjust-
ment in the LTD access level.
Boil SENS = SUP

The type of terminal units that are being used
for the boiler side of the heating system.
Boil SENS = SUP

The design indoor air temperature used in the
heat loss calculation for the boiler system.
Boil SENS = SUP

The design supply temperature used in the heat
loss calculation for the boiler system.
Boil SENS = SUP

The maximum temperature allowed for the
boiler target temperature.
Boil SENS = SUP

The minimum temperature allowed for the boiler
target temperature.
Boil SENS

NONE

80 to 210°F, OFF
(27 to 99°C, OFF)
Default = 140°F (60°C)

D1