Restoring parameters to factory-default values – Rockwell Automation Liqui-Flo 20-HIM-A6 with 2.0 AC Drive User Manual
Page 10
10
Rockwell Automation Publication LIQFLO-UM011B-EN-P - November 2012
Using the 20-HIM-A6 HIM with the LiquiFlo 2.0 AC Drive
5.
Use the
or
key to select Linear List.
6.
Press the
(Enter) key to display either the device’s last-viewed
parameter or the first parameter in the linear list.
7.
Use the
or
key to scroll to the desired parameter.
8.
Press the EDIT ‘soft key’ (for editable parameters only) to display the Edit
Parameter pop-up box (
Figure 9
).
9.
Use the numeric keys, decimal ‘soft key’, and ‘soft key’ to edit the
parameter.
10.
Press the ENTER ‘soft key’ to enter the new parameter value and return to
the parameter screen.
Restoring Parameters to Factory-default Values
To restore all parameters to their factory-default values, perform the following
steps.
1.
Access the Status screen (see
Figure 8
).
2.
Use the
or
key to scroll to the Port of the device whose
parameters you want to set to factory defaults (for example, Port 00 for the
Host Drive or the respective port number for one of the drive’s connected
peripherals).
3.
Press the
key to display its last-viewed folder.
4.
Use the
or
key to scroll to the MEMORY folder.
5.
Use the
or
key to select Set Defaults.
6.
Press the
(Enter) key to display the Set Defaults pop-up box.
Figure 10 - Set Defaults Pop-Up Box
7.
Press the ENTER ‘soft key’ to affirm and set all device parameter values to
factory defaults—or press the ESC ‘soft key’ to cancel.
TIP
When the decimal ‘soft key’ is pressed while editing a numeric value,
this key temporarily changes to an EXP ‘soft key’ to allow exponential
entry.
TIP
Parameter values are retained through a line dip or power shutdown.
Stopped
0.00 Hz
AUTO
F
WARNING
Sets all parameters to
factory defaults.
Continue?
ESC
ENTER