Processor module start up process – Rockwell Automation AADvance Controller Troubleshooting and Maintenance Manual User Manual
Page 51

Document: 553634
(ICSTT-RM406F_EN_P) Issue: 089:
4-7
Processor Module Start Up Process
Note: When inserting more than one processor module they MUST be inserted one at a time and the
module be allowed to educate (in the case of a 2
nd
and 3
rd
processor).
Table 4:
Single Processor Module Installation Procedure (New Processor Module)
Step Task
1.
Install the processor into a processor base unit slot.
2.
All LEDs are off and after applying power the processor will display the following status
indications:
Healthy
Flashes RED for a second then goes GREEN as the module boots up (10
to 20 seconds)
Ready
Will remain OFF as the module boots up (10 - 20 seconds) then goes RED
Run
Will remain OFF as the Module boots up (10 to 20 seconds) then goes
RED
System Healthy Will remain OFF as the Module boots up (10 to 20 seconds) then goes
GREEN
Force
Will remain OFF as the Module boots up (10 to 20 seconds) then stays
OFF until the module has educated.
Aux
Will remain OFF as the Module boots up (10 to 20 seconds) then is
dependent upon data connection.
Serial 1
Will remain OFF as the Module boots up (10 to 20 seconds) then is
dependent upon data connection
Serial 2
Will remain OFF as the Module boots up (10 to 20 seconds) then is
dependent upon data connection
Ethernet 1
Will remain OFF as the Module boots up (10 to 20 seconds) then is
dependent upon data connection
Ethernet 2
Will remain OFF as the Module boots up (10 to 20 seconds) then is
dependent upon data connection
You have to set up the processor IP Address so that the workstation can communicate with the
processor module and download the latest firmware build and configure the processor variables.
3.
Set the Controller IP Address for all the processor modules using the "AADvance Discover
Utility". (Refer to the Configuration Guide for detailed instructions on using the AADvance
Discover Utility Doc. No: 553633.
4.
Install a Program Enable Key. Download a valid application and press the FAULT RESET
button. When the application is downloaded and valid the module will display the following
indications:
Valid Application Downloaded
Healthy
GREEN