6-7
Estimate Module Supply Power Dissipation and Field Loop Power Dissipation
Module supply voltage and field power consumption is dissipated as heat. Use these
tables to estimate the supply voltage and field power heat dissipation of your system.
Note: All figures given are worst-case estimates based upon maximum operating field
current and voltages.
Table 19:
Estimating Module Supply Power Dissipation
Item
Number
of
Modules
Power Dissipation
Subtotal
(W/BTU/hr)
T9110 Processor Module
× 8.0W (27.3BTU/hr) =
T9401 Digital Input Module 24V dc, 8 channel
× 3.3W (11.3BTU/hr) =
T9402 Digital Input Module 24V dc, 16 channel
× 4.0W (13.6BTU/hr) =
T9431 Analogue Input Module, 8 channel
× 3.3W (11.3BTU/hr) =
T9432 Analogue Input Module, 16 channel
× 4.0W (13.6BTU/hr) =
T9451 Digital Output Module, 24V dc, 8 channel
× 3.0W (10.2BTU/h) =
T9482 Analogue Output Module, 8 channel, isolated
× 3.6W (12.3BTU/hr) =
Total:
Table 20:
Estimating Field Loop Power Dissipation
Item
Number
of Field
loops
Maximum Field
Loop Power
Dissipation
Subtotal
(W/BTU/hr)
T9801/2/3 Digital Input Termination Assembly (powered by
the T9401/2 module)
× 0.2W (0.68BTU/hr) =
T9831/2/3 Analogue Input Termination Assembly (powered
by the T9431/2 module)
× 0.08W
(0.27BTU/hr)
=
T9451 Digital Output Module, 24V dc, 8 channel (1A load)
x 0.57W (1.94
BTU/hr)
=
T9482 Analogue Output Module, 8 channel, isolated
× 0.77W
(2.63BTU/hr)
=
Total: