Publication CNET-IN003A-EN-P - January 2006

Overview of the ControlNet Ex Media System 1-9

Two insulator kits are available:

Catalog number 1797-BOOT provides standard BNC trunk cable
insulators.

Catalog number 1797-INS provides a variety of the preformed
boots and insulators used with the ControlNet Ex system
products.

ControlNet Ex System
Installation Requirements

You can connect a maximum of 48 ControlNet Ex taps with a total of
250m of coax cable when using fiber hub architecture. The maximum
distance increases to 1000m when you use only 2 taps.

Refer to Determine Trunk Cable Section Lengths on page 2-4 and see
the table below for more information.

Catalog
Number

Catalog Name

Description

1797-RPA

ControlNet Ex
Modular
Repeater Adapter

Represents one ControlNet Ex
node and must be connected to a
coax trunk cable by

1797-TPx

1797-RPFM

ControlNet Ex
Fiber Repeater
Module, Medium
Distance

Allows connection of a maximum
of two devices per 1797-RPA and
is powered directly by 1797-RPA

1797-ACNR15

Redundant
Media
ControlNet Ex
Adapter

Represents one ControlNet Ex
node and must be connected to a
coax trunk cable by

1797-TPx -each one with two
redundant output channels that
are connected to different
ControlNet Ex networks (coax
cables and 1797-TPx)

1797-BCNR

FLEX Ex
Redundant
ControlNet
Barrier Module

Galvanic isolation barrier for
signal between the non-intrinsic
ControlNet system an
intrinsically-safe ControlNet Ex
system.

1797-TCAP

ControlNet Ex
Tap (Dummy)
Terminator

Represents one ControlNet Ex
node and is a simple capacitor
(56pF) with a coax connector

1797-TPx

ControlNet Ex
Coax Tap

Four types of connections
available: S (straight T-tap), R
(right angle T-tap), YS (straight
Y-tap), and YR (right angle Y-tap) -
a maximum of 48 taps can be
connected by coax trunk cable

1797-XT

ControlNet Ex
Trunk Terminator

Simple resistor (75

) with coax

connector that must be on each
end of the ControlNet Ex coax
trunk for termination