Overview of the ControlNet Ex Media System 1-9
Two insulator kits are available:
•
Catalog number 1797-BOOT provides standard BNC trunk cable
insulators.
•
Catalog number 1797-INS provides a variety of the preformed
boots and insulators used with the ControlNet Ex system
products.
ControlNet Ex System
Installation Requirements
You can connect a maximum of 48 ControlNet Ex taps with a total of
250m of coax cable when using fiber hub architecture. The maximum
distance increases to 1000m when you use only 2 taps.
Refer to Determine Trunk Cable Section Lengths on page 2-4 and see
the table below for more information.
Catalog
Number
Catalog Name
Description
1797-RPA
ControlNet Ex
Modular
Repeater Adapter
Represents one ControlNet Ex
node and must be connected to a
coax trunk cable by
1797-TPx
1797-RPFM
ControlNet Ex
Fiber Repeater
Module, Medium
Distance
Allows connection of a maximum
of two devices per 1797-RPA and
is powered directly by 1797-RPA
1797-ACNR15
Redundant
Media
ControlNet Ex
Adapter
Represents one ControlNet Ex
node and must be connected to a
coax trunk cable by
1797-TPx -each one with two
redundant output channels that
are connected to different
ControlNet Ex networks (coax
cables and 1797-TPx)
1797-BCNR
FLEX Ex
Redundant
ControlNet
Barrier Module
Galvanic isolation barrier for
signal between the non-intrinsic
ControlNet system an
intrinsically-safe ControlNet Ex
system.
1797-TCAP
ControlNet Ex
Tap (Dummy)
Terminator
Represents one ControlNet Ex
node and is a simple capacitor
(56pF) with a coax connector
1797-TPx
ControlNet Ex
Coax Tap
Four types of connections
available: S (straight T-tap), R
(right angle T-tap), YS (straight
Y-tap), and YR (right angle Y-tap) -
a maximum of 48 taps can be
connected by coax trunk cable
1797-XT
ControlNet Ex
Trunk Terminator
Simple resistor (75
Ω
) with coax
connector that must be on each
end of the ControlNet Ex coax
trunk for termination