Ok status indicator and display – Rockwell Automation 1768-CNxxx ControlNet Communication Modules User Manual
Page 43
![background image](/manuals/580919/43/background.png)
Rockwell Automation Publication CNET-IN005C-EN-P - July 2014
43
1756 ControlNet Status Indicators
Appendix A
1756-CNB/E and
1756-CNBR/E ControlNet
Communication Modules
This section provides the following information about status indicators:
• To understand the OK status indicator and display messages, see
Table 4
.
• For information about viewing the network channel status indicators
together, see
Table 5 on page 46
.
• For information about viewing the network channel status indicators
individually, see
Table 6 on page 46
.
OK Status Indicator and Display
Table 4 - OK Status Indicator and Display
Status
Display
Description
Off
None
The module is not communicating due to a power supply fault or internal fault.
Do any of the following:
• Check the power supply.
• Check the cable connectors.
• Make sure the module is firmly seated in the chassis.
• If the status indicator remains off, replace the module.
Steady red
Msg scrolls
(1)
The module’s network address is set to 00, an invalid ControlNet address, or 99, an invalid ControlNet address if you are
using enhanced redundancy control. See the footnote at the end of the table.
Remove the module from the chassis, and set the network address to a valid value. For more information,
see
Install a 1756 ControlNet Communication Module on page 9
BPA# ERR
The module has detected a different slot address from that latched in when the module was started. Excessive noise on the
backplane causes this error.
Replace the chassis or module.
BPRX ERR
Too many CRC errors are being generated by the multicast backplane receiver, so the backplane multicast receivers have
been shut off.
Replace the module.
BPIC ERR
Hardware within the module has faulted.
Replace the module.
CNIC ERR
DUPL NODE
For enhanced redundancy systems, this may be a temporary condition during chassis switchover. Otherwise, the module’s
network address is the same as another module’s on the link.
For enhanced redundancy systems only, wait 10 seconds. If the condition persists, remove the module from the chassis,
and set the switches to a unique address. For more information,
see
Install a 1756 ControlNet Communication Module on page 9
RACK ERR
The module cannot read the backplane EEPROM, or the rack/slot address is incorrect.
Replace the chassis.
STOP
The 1756-CNB/E module was commanded to stop functioning by the redundancy module. This occurs when a non-
redundancy-compliant 1756-CNB/E module is placed into a redundant secondary chassis.
Remove the nonredundancy-compliant 1756-CNB/E module from the redundant secondary chassis and replace it with a
redundant 1756-CNBR/E module.
WAIT RM
(2)
or
WAIT SRM
(2)
The 1756-CNB/E module is waiting for the redundancy module to be started.
Flashing red
BOOT
The module has invalid firmware.
Update the module’s firmware with ControlFLASH software.
ROM UPDT
A firmware update is in progress.
SNGL KPR!
The module has detected that it has been connected to a ControlNet single-keeper network, version 1.0 or 1.25.
Update the firmware of module at node address 01 and reschedule the network.