Network channel status indicators – Rockwell Automation 1768-CNxxx ControlNet Communication Modules User Manual
Page 42

42
Rockwell Automation Publication CNET-IN005C-EN-P - July 2014
Appendix A
1756 ControlNet Status Indicators
Network Channel Status Indicators
Table 2 - Network Channel Status Indicators A and B
Status
Description
Off
There is no power.
Steady red
Unit has faulted.
Cycle power or reset unit. If the fault persists, contact a Rockwell Automation representative or distributor.
Alternating red/green
A self-test is being conducted.
Alternating red/off
Node has been configured incorrectly.
Check network address and other ControlNet configuration parameters.
Table 3 - Network Channel Status Indicators A or B
Status
Description
Off
Channel has been disabled.
Program the network for redundant media, if required.
Steady green
This is normal operation.
Flashing green/off
Temporary errors exist. The unit will self-correct.
Node is not configured to go online.
Make sure that the configuration manager node (keeper) is present and working and the selected address is not greater
than the maximum unscheduled node address (UMAX).
(1)
Flashing red/off
A media fault exists.
Check media for broken cables, loose connectors, or missing terminators.
No other nodes are present on the network.
Add other nodes to the network.
(1) The configuration manager node (keeper) is the node responsible for distributing ControlNet configuration data to all nodes on the network.