Redundant media, Installation summary, Grounding considerations – Rockwell Automation 1768-CNxxx ControlNet Communication Modules User Manual
Page 25: Set the node address, Redundant media installation summary

Rockwell Automation Publication CNET-IN005C-EN-P - July 2014
25
Install a 1768 ControlNet Communication Module
Chapter 2
Redundant Media
The 1768-CNBR bridge module has two ControlNet ports to support
redundant media. For information about using the module with redundant
media, see
.
Installation Summary
To install a communication module in a 1768 ControlLogix chassis, complete
these steps.
1.
2.
.
3.
Connect the Module to a ControlNet Network
Grounding Considerations
Set the Node Address
Use a small screwdriver to set the module’s node address switches. You must
specify a unique ControlNet node address. You can select an address of 01…99.
Address 00 is an invalid ControlNet node address.
ATTENTION: This product is grounded through the DIN rail to chassis ground.
Use zinc-plated yellow-chromate steel DIN rail to assure proper grounding. The
use of other DIN rail materials (for example, aluminum or plastic) that can
corrode, oxidize, or are poor conductors, can result in improper or intermittent
grounding. Secure DIN rail to mounting surface approximately every 200 mm
(7.87 in.) and use end-anchors appropriately.
NETWORK
ADDRESS
31651- M
50
60
6
8
7
70
9
0
4
3
2
1
5
80
90
00
10
20
30
40
NETWORK
ADDRESS
50
60
6
8
7
70
9
0
4
3
2
1
5
80
90
00
10
20
30
40
Top of Module
Back of Modul
e
This module’s node address is 21.