Required tools, Install the computer, Panel mounting guidelines – Rockwell Automation 6189x Integrated Display Industrial Computers User Manual User Manual
Page 28: Required tools install the computer
28
Rockwell Automation Publication 6181P-UM003A-EN-P - May 2014
Chapter 2
Installation
Required Tools
These tools are required for computer installation:
• #2 cross-head screwdriver
• Panel cutout tools (for panel mounting)
• Drill motor and drill bit (for wall, machine, and table mounting)
• Antistatic wrist strap
Install the Computer
The computers support the following mounting options:
• Panel mount (display computer models)
• Wall, machine, table, and bookshelf mounts (non-display computer models)
Panel Mounting Guidelines
Observe these guidelines when installing the computer in a panel:
• Remove all electrical power from the panel before making the cutout.
• Confirm that there is adequate space behind the panel. For specific
Mounting Clearance Requirements
• Cut supporting panels to specifications before installation. Take precautions
so metal cuttings do not enter components already installed in panel.
Supporting panels must be at least 14 gauge for proper sealing against water
and dust and to provide proper support. The mounting hardware supplied
accommodates panel thickness between 1.5…5.5 mm (0.06…0.22 in.).
• Make sure the area around the panel cutout is clear.
• Certain restrictions apply when mounting a display computer in a panel.
for details.
Figure 14 - Acceptable and Unacceptable Mounting Positions for Display Computers
ATTENTION: Failure to follow these guidelines can result in personal
injury or damage to the panel components.
Acceptable
Unacceptable
In either position, front USB port
must be near bottom of display.
≤60°
from Vertical
≤60°
from Vertical