46 FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules
Publication
1797-5.5 - September 2011
apparatus and the approved values of C
a
and L
a
of the associated apparatus
are greater than C
i
+ C
cable
and L
i
+ L
cable
respectively for the intrinsically safe
apparatus. The internal capacitances of C
i
of the terminal base must be taken
into account to verify the intrinsic safety.
Simple apparatus is defined as a device which neither generates nor stores
more than 1.2V, 0.1 A, 20
μ
J, or 25 mW.
Wiring methods must be in accordance with the National Electric Code,
ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric Code CSA
C22.1, Part 1, Appendix F. For additional information refer to ANSI/ISA
RP12.6.
This module, 1797-IE8, must be used with terminal base 1797-TB3 or
1797-TB3S.
Terminals 3, 7, 11, 15, 20, 24, 28, 32, 36-39, and 46 to 49 shall not be
connected.
WARNING
: Substitution of components may impair intrinsic safety.
AVERTISSEMENT:
La substitution de composant peut compromettre la
securite intrinseque.
1797-IE8, 1797-IE8H, and 1797-IE8NF FM I/O Entity Parameters
If this product has the FM mark, it has been designed, evaluated, tested, and
certified to meet the following standards:
•
FM C1. No.3600:1998, Electrical Equipment for Use in Hazardous
(Classified) Locations General Requirements
•
FM C1. No.3610:1999, Intrinsically Safe Apparatus and Associated
Apparatus for Use in Class I, II, III Division 1 Hazardous (Classified)
Locations
•
FM C1. No.3615:1989, Explosionproof Electrical Equipment General
Requirements
•
FM C1. No.3810:1989, 1995, Electrical and Electronic Test,
Measuring and Process Control Equipment
•
ANSI/NEMA 250, 1991, Enclosures for Electrical Equipment