Rockwell Automation 1797-IE8NF FLEX Ex 8 Input Analog, HART and Noise Filter Module User Manual
Page 44
44 FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules
Publication
1797-5.5 - September 2011
Wiring Methods
•
Wiring method 1 - Each channel is wired separately.
•
Wiring method 2 - Multiple channels in one cable, providing each
channel is separated in accordance with the National Electric Code
(NEC) or Canadian Electric Code (CEC).
Table 1
Wiring
Method
Channel
Terminals
V
oc
(V)
I
sc
(mA)
V
t
(V)
I
t
(mA)
Groups
C
a
(
μ
F)
L
a
(mH)
1 and 2
Any one
channel,
for
example,
ch0
0(+), 1(sig)
23.7
92.5
-
-
A, B, IIC
0.06
2.0
C, E, IIB
0.18
8.0
D, F, G, IIA
0.48
16.0
1(sig), 2(-)
5
1.0
-
-
A, B, IIC
100
1000
C, E, IIB
300
1000
D, F, G, IIA
800
1000
0(+), 1(sig),
2(-)
-
-
23.7
93.5
A, B, IIC
0.06
2.0
C, E, IIB
0.18
8.0
D, F, G, IIA
0.48
16.0
FLEX Ex Analog
Input I/O Module
Indicators
Female Bus
Field Wiring
Terminal Base
Terminal Base
Key
Male Bus
Connection
Key Position for
Terminal Base
Insertion
42055