Error level 0.1 ma steps – Rockwell Automation 1797-IE8NF FLEX Ex 8 Input Analog, HART and Noise Filter Module User Manual
Page 24
24 FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules
Publication
1797-5.5 - September 2011
6
0 1 1 0 4…20 mA as
⎟
%
4.00
22.00
0
(0%)
10607
(106.07%)
0.17% of
4...20 mA
7
0 1 1 1 4…20 mA as
unsigned
integer
4.00
20.00
0
(4 mA)
65535
(20 mA)
0.03% of
4...20 mA
8
1 0 0 0 Not assigned
9
1 0 0 1
10
1 0 1 0
11
1 0 1 1 0...20 mA as
A/D count
0.00
22.00
0
(0 mA)
55000
(22 mA)
0.04% of
0...20 mA
12
1 1 0 0 4...20 mA as
%
3.60
21.00
-250
(-2.50%)
10625
(106.25%)
0.16% of
4...20 mA
13
1 1 0 1 4...20 mA as
%
3.00
21.00
-625
(-6.25%)
10625
(106.25%)
0.16% of
4...20 mA
14
1 1 1 0 4...20 mA as
%
2.00
22.00
-1250
(-12.50%)
11250
(112.50%)
0.16% of
4...20 mA
15
1 1 1 1 Not assigned
Error Level 0.1 mA Steps
Word
Bits
Description
Word 0
13
12
11
10
09
Error level channels 0...3
Word 1
13
12
11
10
09
Error level channels 4...7
0
0
0
0
0
Disabled
0.1 mA * binary valve = remote fault alarm
Examples
Data Format
2...22 mA
-12.5...112.5%
0
0
1
1
1
Binary value = 7, 0.1 mA * 7 = 0.7 mA
Remote fault alarm at -4.38% or +104.38%
0
1
1
1
1
Binary value = 15, 0.1 mA * 15 = 1.5 mA
Remote fault alarm at -9.38% or + 109.38%
Data Format - Write Words 2 and 3 (Continued)
Data
Format
Bits
Format
Signal Range User Range
Resolution
15 14 13 12
11 10 9
8
7
6
5
4
LO
HI
LO
HI
3
2
1
0