1797-ie8h input map (read words) – Rockwell Automation 1797-IE8NF FLEX Ex 8 Input Analog, HART and Noise Filter Module User Manual
Page 18

18 FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules
Publication
1797-5.5 - September 2011
1797-IE8H Input Map (Read Words)
Word
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
Input Data Channel 0
1
Input Data Channel 1
2
Input Data Channel 2
3
Input Data Channel 3
4
Input Data Channel 4
5
Input Data Channel 5
6
Input Data Channel 6
7
Input Data Channel 7
8
HA
Ch 7
HA
Ch 6
HA
Ch 5
HA
Ch 4
HA
Ch 3
HA
Ch 2
HA
Ch 1
HA
Ch 0
LA
Ch 7
LA
Ch 6
LA
Ch 5
LA
Ch 4
LA
Ch 3
LA
Ch 2
LA
Ch 1
LA
Ch 0
9
SA
Rem.
Ch 7
SA
Rem.
Ch 6
SA
Rem.
Ch 5
SA
Rem.
Ch 4
SA
Rem.
Ch 3
SA
Rem.
Ch 2
SA
Rem.
Ch 1
SA
Rem.
Ch 0
OR
Ch7
OR
Ch6
OR
Ch5
OR
Ch4
OR
Ch3
OR
Ch2
OR
Ch1
OR
Ch0
10
Reserved
HR Reserved
Diagnostic Status
11
HCF
Ch 7
HCF
Ch 6
HCF
Ch 5
HCF
Ch 4
HCF
Ch 3
HCF
Ch 2
HCF
Ch 1
HCF
Ch 0
HF
Ch 7
HF
Ch 6
HF
Ch 5
HF
Ch 4
HF
Ch 3
HF
Ch 2
HF
Ch 1
HF
Ch 0
12
HP
Ch 7
HP
Ch 6
HP
Ch 5
HP
Ch 4
HP
Ch 3
HP
Ch 2
HP
Ch 1
HP
Ch 0
HC
Ch 7
HC
Ch 6
HC
Ch 5
HC
Ch 4
HC
Ch 3
HC
Ch 2
HC
Ch 1
HC
Ch 0
Where: HA = high alarm
LA = low alarm
SA = second alarm
OR = out of range
Res. = reserved
HR = HART rebuilding
HCF = HART current fault
HF = HART communication fault
HP = HART present
HC = HART communication