Rockwell Automation 1797-IE8NF FLEX Ex 8 Input Analog, HART and Noise Filter Module User Manual
Page 40
![background image](/manuals/580680/40/background.png)
40 FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules
Publication
1797-5.5 - September 2011
Functional Data Range
>17V @ 22 mA
>23V @ 0 mA
Data Format
Configurable
Step Response to
99% of FS
80 ms
Module from Adapter
Best/Worst Update Time
200 ms/1600 µs
Indicators
8 red fault indicators
8 yellow channel indicators
1 green power indicator
Inputs (Intrinsically Safe)
(Terminals: 0…2; 4…6;
8…10; 12…14; 17…19;
21…23; 25…27; 29…31)
U
o
< 24.4V
I
o
< 92.5 mA
P
o
< 565 mW
Isolation Path
Input to Power Supply
Input to Flexbus
Input to Input
Power Supply to
Flexbus
Isolation Type
Galvanic to DIN EN60079-11
Galvanic to DIN EN60079-11
None
Galvanic to DIN EN60079-11
Power Supply
(+V, -V intrinsically safe)
(Terminals: 34/50 (+):
35/51 (-))
U
i
< 9.5V dc
I
i
< 1 A
L
i
= Negligible
C
i
= 120 nF
Module Field-side Power
Consumption
7.1 W
Power Dissipation
3.9 W
Thermal Dissipation
13.5 BTU/hr
Module Location
Cat. No. 1797-TB3 or 1797-TB3S
Conductor Wire Size
4 mm
2
(12 AWG) stranded max
1.2 mm (3/64 in.) insulation max
Dimensions
Metric
Imperial
46 mm x 94 mm x 75 mm
(1.8 in. x 3.7 in. x 2.95 in.)
Weight
200 g (approximately)
Keyswitch Position
8
Environmental Conditions
Operational Temperature -20…+70
o
C (-4…+158
o
F)
Storage Temperature
-40…+85
o
C (-40…+185
o
F)
Relative Humidity
5…95% noncondensing
Shock
Operating Tested to 15 g peak acceleration, 11(+1) ms pulse width
Nonoperating
Tested to 15 g peak acceleration, 11(+1) ms pulse width
Vibration
Tested 2 g @ 10…500 Hz per IEC68-2-6