CIP Error Message Codes
CIP Error Message Codes
Error ID
Description
33
Parameter configuration errors.
Sub Error ID
Description
32
Bad channel number
36
Unsupported CIP connection type
40
Unsupported CIP symbolic data type
41
Invalid CIP symbol name
42
Unsupported CIP class value or member ID count
48
Function block’s input data array size is not sufficient
49
Invalid target path
50
Bad service code
51
Function block’s transmit data array size is too big for CIP
communication
55
Timeout errors
Sub Error ID
Description
112
Message timed out while waiting in message wati queue
113
Message timed out while waiting for link layer/connection
establishment.
114
Message timed out while waiting for transmit to link layer.
115
Message timed out while waiting for response from link layer.
69
Server response format error codes.
Sub Error ID
Description
65
Message reply not matching with request.
68
Message reply data type not valid/supported
(MSG_CIPSYMBOLIC)
208
No IP address configured for the network.
209
Maximum number of connections used - no connections available.
210
Invalid internet address or node address.
217
Message execution was cancelled by user. Cancel parameter was set to TRUE.
218
No network buffer space available.