beautypg.com

Indicators, Comm, module, and power status indicators – Rockwell Automation 1797-ACNR15 ControlNet Ex Redundant Media Adapter User Manual

Page 25

background image

ControlNet Ex Redundant Media Adapter 25

Publication

1797-5.14 - March 2010

FM 1797-ACNR15 I/O Entity Parameters

Indicators

The figure below identifies indicators on the adapter module.

Comm, Module, and Power Status Indicators

Terminals

V

t

(V)

I

t

(mA)

Groups

C

a

(

μF)

L

a

(

μH)

Male Bus
Connector

5.8

400

A-G

3.0

3.0

Status Indicators

Probable Cause

Comm A and Comm B Simultaneously

Off

No power, or reset

Red

Adapter inoperative

Red/Grn - (Flashing
Alternately)

Adapter self-test

Red/Off - (Flashing
Alternately)

Bad node configuration (duplicate address)

PWR

1797-ACNR15

3

2

41412

Module Status

Comm A

Comm B

Power