beautypg.com

Cenelec installation label – Rockwell Automation 1797-ACNR15 ControlNet Ex Redundant Media Adapter User Manual

Page 19

background image

ControlNet Ex Redundant Media Adapter 19

Publication

1797-5.14 - March 2010

Certification Specific ControlNet Ex System Diagrams

The following pages include certification specific ControlNet Ex system
diagrams and notes pertaining to these diagrams. Select either CENELEC,
UL, C-UL, or FM and follow the requirements of that diagram as you
configure and install your system.

CENELEC Installation Label

A label with this system marking must be attached near the main components
of the system. If the system is installed in a cabinet, this label must be fixed
inside the cabinet.

CENELEC 1797-ACNR15 I/O Entity Parameters

Terminals

U

o

(V)

I

o

(mA)

Groups

C

o

(

μF)

L

o

(

μH)

Male Bus
Connector

5.4

400

IIB/IIC

65

10

0102

ControlNet Ex System

Allen-Bradley

Attention!
Avoid electrostatic charging!

-20

0

C <= Ambient Temperature <= +70

0

C

1 Allen-Bradley Dr.
Mayfield Hts., OH USA

DMT 99 ATEX E 065 X
II (1)2G Ex ia ib IIC