beautypg.com

Rockwell Automation 1797-ACNR15 ControlNet Ex Redundant Media Adapter User Manual

Page 15

background image

ControlNet Ex Redundant Media Adapter 15

Publication

1797-5.14 - March 2010

3. Apply +V and -V power to the adapter through a removable terminal

block.

Screw terminals and spring terminals are provided.

4. Strip the +V and -V wires to a length so no bare conductor shows

after inserting the wires into position (+V, -V).

5. If you are using the spring terminals of the plug, insert a screwdriver

into the slot and carefully pry until the spring clamp opens to accept
the wire.

6. Set the network address using the 2-position push-switch G.

Valid settings range from 01 to 99. Press either the + or - buttons to
change the number.

WARNING

Do not remove or replace an adapter when power is applied.
Interruption of the bus can result in unintended operation or
machine motion.
Do not use any unused terminals on this adapter. Using these
terminals as supporting terminals can result in damage to the
module, or unintended operation of your system.
Make certain that you power this adapter with an intrinsically
safe power supply. Do not exceed the values listed in the
specifications for this adapter.

+V -V +V -V

+V -V +V -V

41297