UL, C-UL ControlNet Ex System Diagram Notes

The entity concept allows interconnection of intrinsically safe apparatus

with associated apparatus not specifically examined in combination as a
system when the approved values of V

oc

and I

sc

or V

t

and I

t

of the associated

apparatus are less than or equal to V

max

and I

max

of the intrinsically safe

apparatus and the approved values of C

a

and L

a

of the associated apparatus

are greater than C

i

+ C

cable

and L

i

+ L

cable

respectively for the intrinsically safe

apparatus.

Wiring methods must be in accordance with the National Electric Code,

ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric Code CSA
C22.1, Part 1, Appendix F. For additional information refer to ANSI/ISA
RP12.6.

WARNING: Substitution of components may impair intrinsic safety.

AVERTISSEMENT: La substitution de composant peut compromettre la
securite intrinseque.

If fiber optic cable is provided with a metal shield, it must be connected

to a dedicated intrinsic safety ground in the nonhazardous location and tied
back in the hazardous location or be connected to a ground in the hazardous
location and tied back in the nonhazardous location.

The glass fiber must have a minimum diameter of 6 μm.

UL, C-UL 1797-ACNR15 I/O Entity Parameters

Terminals

V

t

(V)

I

t

(mA)

Groups

C

a

(

μF)

L

a

(

μH)

Male Bus
Connector

5.8

400

A-G

3.0

3.0