Resister Device Compatibility
The following table lists the specifications for the resistance devices that
you can use with the module.
Hardware Features
The RTD/resistance module contains either a fixed terminal block (or a
removable D-sub connector) providing connections for four 3-wire inputs
for any combination of RTD and resistance input devices. Channels are
wired as differential inputs. The illustration below shows the hardware
features of the module.
Table 1.2 Resistance Device Specifications
Resistance Type
Range
Scaling
(Counts)
Resolution*
Accuracy (0 to 55°C)**
Resistance 100m
Ω
1 to 650
Ω
10 to 6250
100m
Ω
+1.25
Ω
Resistance 10m
Ω
1 to 327
Ω
100 to 32700
10
Ω
+0.65
Ω
*Filter set for 10 Hz
**Module only
Node Address
Switches
Module and Network
Status Indicators
43223
1790D-4R0/T4R0 DeviceNet Module
RTD/resistance
Channel Indicators
RTD/resistance Connections
(D-sub Connector shown)
CompactBlock LDX
1790D-8BV8V
8 INPUTS/8OUTPUTS-DC POWER
0
7
0
7
DeviceNet Network
Connection
DIN Rail Slot
Panel Mount
Hole