2 - installation and wiring, Before you begin, Power requirements – Rockwell Automation 1790P-4R0 CompactBlock LDX I/O RTD/Resistance Input Module User Manual
Page 13: 1790d-4r0/t4r0, 1790p-t4r0, Installation and wiring, Chapter
1
Publication 1790-UM002A-EN-P
Chapter
2
Installation and Wiring
Before You Begin
This chapter tells you how to:
•
determine the power requirements for the modules
•
avoid electrostatic damage
•
install the module
•
wire the module’s terminal block
Power Requirements
1790D-4R0/T4R0
The module receives system power from the DeviceNet network. An
auxiliary field supply provides power for the RTD/resistance channels.
1790P-T4R0
The module requires external supplies for both system power and for the
RTD/resistance channels.
Table 2.1 1790D-4R0/T4R0 Power Specifications
Power
Specification
DeviceNet
Supply voltage - 24V dc nominal
Voltage range - 11-28.8V dc
Power dissipation - 1.2W maximum @ 28.8V dc
Field
Supply voltage - 24V dc nominal
Voltage range - 21.6-26.4V dc (+10%)
Power dissipation - 1.5W maximum @ 26.4V dc
Table 2.2 1790P-T4R0 Power Specifications
Power
Specification
PROFIBUS
Supply voltage - 24V dc nominal
Voltage range - 19.2-28.8V dc
Power dissipation - 2W maximum @ 28.8V dc
Field
Supply voltage - 24V dc nominal
Voltage range - 21.6-26.4V dc (+10%)
Power dissipation - 1.5W maximum @ 26.4V dc