Download the configuration – Rockwell Automation 1790P-4R0 CompactBlock LDX I/O RTD/Resistance Input Module User Manual
Page 63
![background image](/manuals/579946/63/background.png)
Publication 1790-UM002A-EN-P
Module Configuration for PROFIBUS C-7
Download the
Configuration
To download the configuration:
1. Verify that the processor is in Program Mode.
2. Make sure the serial communication cable is connected between the
PC comm port and the scanner serial port.
3. Highlight Master in the Network pane.
4. Right click to select Connect from the menu. (Or, choose
Edit>Connect).
You may be prompted with a message indicating a configuration
mismatch between what is in the scanner and your current PROFIBUS
project. In this case, select Yes to retain your configuration.
Any configuration mismatches display for the Master status.
Highlight the Master and then right
click to select Connect.