Rockwell Automation 1734-XXXX POINT I/O and ArmorPOINT I/O DeviceLogix User Manual User Manual
Page 87
Publication 1734-UM015A-EN-E - November 2009
Troubleshooting 85
Network Status
DeviceLogix Status
I/O Status
Indication
Probable Cause
Recommended Action
Off
Device is not online.
- Device has not completed
dup_MAC_id test.
- Device not powered - check module
status indicator.
Apply power to device, wait for
dup_MAC_id to complete, and
correct, as needed.
Green
Device is online and has connections
in the established state.
None.
Flashing
green
Device is online but has no
connections in the established state.
None .
Flashing red
One or more I/O connections are in
the timed-out state.
This could also mean a peer is not
producing data at all, or it is not
configured correctly.
Check I/O connection with
master. Verify peers are present
and configured properly.
Red
Critical link failure - failed
communication device. Device
detected error that prevents it
communicating on the network.
Verify that adapter and terminal
bases are properly installed, and
reinstall, as needed.
Flashing
red/green
Device is in self-test.
None.
Indication
Probable Cause
Recommended Action
Off
DeviceLogix program is not
controlling outputs.
None.
Green
DeviceLogix program is controlling
outputs.
None.
Flashing
green
At least one input in DeviceLogix
program is forced on/off.
None.
Indication
Probable Cause
Recommended Action
Off
Input or output is in the OFF state.
None.
Yellow
Input or output is in the ON state.
None.