Publication 1788-UM052B-EN-P - April 2002
Troubleshooting and Common Questions B-3
Device Problems
If you receive a status of Bad:Device Failure, set the RESTART
parameter in the Block window to Processor or Default. If the
problem persists, replace the device.
If a device does not accept a permanent address, you must set the
device tag. For instructions on setting the tag, refer to the Setting
Device or Block Tags on page 4-5. If the device already has a tag, the
T3 network parameter might not be the right length. To solve this
problem, remove the device from the active bus and configure its
address separately.
If a device does not accept a new tag, it might be in an invalid state.
To solve this problem, power the device off and on.
Missing Devices
If a device does not appear in the Project window, complete these
steps:
1. Check all connections.
2. Power on the bus.
3. Select Start
⇒
Programs
⇒
NI-FBUS
⇒
Interface Config and
click on the Advanced button.
4. Set the following parameter values.
5. Select Start
⇒
Programs
⇒
NIFBUS
⇒
nifb to restart the nifb
process.
6. Select Start
⇒
Programs
⇒
NIFBUS
⇒
NI-FBUS Configurator
to restart the NI-FBUS Configurator.
Parameter
Value
Number of unavailable nodes
0
InterPduDelay
20
Slot time
10
Max reply delay
8