Rockwell Automation 1788-FFCT NI-FBUS Configurator User Manual User Manual
Page 69

Publication 1788-UM052B-EN-P - April 2002
Error Messages and Warnings A-3
NIFCONF_ERR_MACROCYCLE_CONFLICT
This macrocycle conflicts with a previously defined macrocycle time for a
device in this loop. Devices can only schedule one macrocycle time. The best
solution is to increase the macrocycle time of the loop that contains the other
block(s) for this device.
NIFCONF_ERR_MACROCYCLE_NOT_GOOD_MULTIPLE
This macrocycle is a bad choice in comparison to the other macrocycles.
NIFCONF_ERR_MACROCYCLE_TOO_SHORT
There was not enough time in this macrocycle to schedule all the function
blocks and parameters. Increase the macrocycle time of the loop to get more
free time.
NIFCONF_ERR_MAXIMUM_LOOPS_EXCEEDED
The maximum number of loops that you can configure on this link has been
exceeded.
NIFCONF_ERR_MISSING_NIFBUS_PATH
The install path for NI-FBUS Configurator is not in the Windows registry.
NIFCONF_ERR_MULTI_LAS
Multiple primary Link Active Schedulers are defined. Only one primary LAS is
allowed on a link.
NIFCONF_ERR_MULTI_TM
Multiple time masters are defined. Only one time master per link is allowed.
NIFCONF_ERR_NO_CONVERSION
There is no conversion for this data type.
NIFCONF_ERR_NO_DATA
No data.
NIFCONF_ERR_NO_LAS_SELECTED
A schedule has been created but no LAS is selected.
NIFCONF_ERR_NO_LM_SELECTED
A schedule has been created but no link master is selected.
NIFCONF_ERR_NO_OBJECT_SELECTED
Nothing is selected.
NIFCONF_ERR_NO_PRINTER_DEVICE_CONTEXT
The NI-FBUS Configurator cannot draw the document because of an incorrect
device context for the selected printer.
NIFCONF_ERR_NO_TM_SELECTED
No time master is selected.
NIFCONF_ERR_NO_UNSCHEDULED_TIME_LEFT
The auto scheduler ran out of unscheduled time. Increase the macrocycle
time(s) to allow more free time for scheduling.
NIFCONF_ERR_NOT_ON_LINK
This object does not belong on this link.
NIFCONF_ERR_OD_SIZE_MISMATCH
The size of the actual data object does not match the object dictionary (OD)
size.
NIFCONF_ERR_OUT_OF_MEMORY
Memory is low; the NI-FBUS Configurator cannot allocate objects. Close
windows to solve this problem.
NIFCONF_ERR_PARAMETER_SCHEDULE_CONFLICT
A parameter communication has already been scheduled for this time. Do not
schedule more than one parameter communication at a time on the fieldbus.
NIFCONF_ERR_REGISTRY_ERROR
Some registry information for your application is missing or corrupt. You might
need to reinstall the NI-FBUS software and the NI-FBUS Configurator. Refer to
your getting started manual for installation instructions.
NIFCONF_ERR_STANDARD_DD_MISSING
The NI-FBUS Configurator could not find the standard DD file.
NIFCONF_ERR_STRING_NOT_FOUND
There is a missing resource string.
NIFCONF_ERR_TEMPLATE_NOT_ASSIGNED
The template is not assigned to a valid project object.
NIFCONF_ERR_TOO_MANY_FB_SCHEDULE_ENTRIES
The schedule for this object contains too many entries for the function block
schedule of the device. Normally, bad choices for macrocycle times cause this
error. Use macrocycle times that are integer multiples of each other to correct
this problem.
Error