Rockwell Automation 1734-XXXX POINT I/O Digital and Analog Modules and POINTBlock I/O Modules User Manual
Page 159

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013
Default Data Maps 167
Produce 1 (Rx)
SC 3
SC 2
SC 1
SC 0
OW 3
OW 2
OW 1
OW 0
Consume (Tx)
No consumed data
Where: OW = open wire, SC = short circuit, fault = open wire or short circuit.
Data Map - Produced Assembly Instance 23
Message Size: 1 Byte
7
6
5
4
3
2
1
0
Produce 0 (Rx)
Fault 3
Fault 2
Fault 1
Fault 0
Input 3
Input 2
Input 1
Input 0
Consume (Tx)
No consumed data
Where: Fault = open wire or short circuit.
Default Data Map - Configuration Assembly Instance 103
Message Size: 18 Bytes
7
6
5
4
3
2
1
0
Consume 0
Input 0 Off to On Filter Byte 0
Consume 1
Input 0 Off to On Filter Byte 1
Consume 2
Input 0 On to Off Filter Byte 0
Consume 3
Input 0 On to Off Filter Byte 1
Consume 4
Input 1 Off to On Filter Byte 0
Consume 5
Input 1 Off to On Filter Byte 1
Consume 6
Input 1 On to Off Filter Byte 0
Consume 7
Input 1 On to Off Filter Byte 1
Consume 8
Input 2 Off to On Filter Byte 0
Consume 9
Input 2 Off to On Filter Byte 1
Consume 10
Input 2 On to Off Filter Byte 0
Consume 11
Input 2 On to Off Filter Byte 1
Consume 12
Input 3 Off to On Filter Byte 0
Consume 13
Input 3 Off to On Filter Byte 1
Consume 14
Input 3 On to Off Filter Byte 0
Consume 15
Input 3 On to Off Filter Byte 1
Consume 16
Autobaud Disable
Enable OW3
Enable OW2
Enable OW1
Enable OW0
Consume 17
Produced Assembly Instance
Produce (Tx)
No produced data
Where: OW = open wire.
Default Data Map - Produced Assembly Instance 101
Message Size: 2 Bytes