Appendix

Publication 1775Ć10.1 - March 1996

Troubleshooting and

Specifications

If you don’t see the power-supply module indicators lit as specified
on page 3-2, use the following table to troubleshoot the problem.

Indicator:

Normal Operation:

If Not Lit:

AC ON

red

no ac power is being supplied to the unit

AC OK

green

an insufficient amount of ac power is being

supplied to the unit

DC OK

green

the supply's internal dc voltages are not in their

proper operating range

If the AC ON indicator is lit and either the AC OK or DC OK
indicators are not lit, you must shut down ac power (or toggle the
remote on/off for the PLC-3/10 chassis or lift and return the module
interlock bar on the PLC-3 chassis) to reset the supply. If this does
not clear the situation, you must troubleshoot the chassis using the
PLC-3 Family Controllers Installation and Operation Manual,
publication number 1775-6.7.1.

Specifications for PLC-3 processors follow.

PLCĆ3 System
I/O Capacity

G

4096 inputs and 4096 outputs maximum

Memory Capacity

G

1.92M words maximum

G

16 bits per word

Data Table Size

G

Expandable (limited only by available

memory)

Scan Time (nominal)

G

1 ms per 1K words of relayĆtype

instructions

G

2.5ms per 1K words (typical)

1775ĆP1 Power Supply

Input Voltage

G

120V AC: 97 to 132V AC

G

220/240V AC: 194 to 264 V AC

Memory Type

G

Error Detecting and Correcting (EDC)

Alternate Language Modules

G

1775ĆS4B scanner module

G

1775ĆGA module

Environmental Conditions

G

Operational Temperature:

0 to 60

°

C (32 to 140

°

F)

G

Storage Temperature:

Ć40 to 85

°

C (Ć40 to 185

°

F)

G

Relative Humidity: 5 to 95%

(without condensation)

PowerĆsupply Module

Indicators

Specifications