1769-BOOLEAN Module Specifications 67
Output Specifications
Environmental Specifications
Attribute
Value
Voltage Category
24V dc
Operating Voltage Range
20.4…26.4V dc (source
(3)
)
(3)
Sourcing Output - Source describes the current flow between the I/O module and the field device. Sourcing output circuits
supply source current to sinking field devices. Field devices connected to the negative side (dc common) of the field power
supply are sinking field devices. Europe: DC sinking input and sourcing output module circuits are the commonly used options.
Number of Outputs
4
Signal Delay, Max (resistive load)
Turn-on: 10 µs, output on-state current > 5 mA
Turn-off: 10 µs, output on-state current > 5 mA
Off-state Leakage, Max
(1)
(1)
Typical Loading Resistor - To limit the effects of leakage current through solid state outputs, a loading resistor can be
connected in parallel with your load. Use a 5.6 kohm, 1/2 W resistor for transistor outputs, 24V dc operation.
1.0 mA @ 26.4V dc
On-state Current, Min
1.0 mA
On-state Voltage Drop, Max
1.0V dc @ 1.0 A
Continuous Current per Point, Max
0.5 A @ 60 °C (140 °F)
1.0 A @ 30 °C (86 °F)
Refer to Temperature Derating.
Surge Current, Max
(2)
(2)
Recommended Surge Suppression - Use a 1N4004 diode reverse-wired across the load for transistor outputs switching 24V dc
inductive loads. For additional details, Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley publication
1770-4.1.
2.0 A (Repeatability is once every 2 s for a duration of
10 ms.)
Output Point to Bus (CompactBus) Isolation
Verified by one of the following dielectric tests: 1200V
ac for 1 s or 1697V dc for 1 s
75V dc working voltage (IEC Class 2 reinforced
insulation)
Attribute
Value
Storage Temperature
-40…85 °C (-40…185°F)
Operating Temperature
0…60 °C (32…140 °F)
Operating Humidity
5…95% noncondensing
Operating Altitude
2000 m (6561 ft)
Vibration, Operating
10…500 Hz, 5 g, 0.030 in. max peak-to-peak
Shock, Operating
Shock, Nonoperating
30 g panel mounted (20 g DIN-rail mounted)
40 g panel mounted (30 g DIN-rail mounted)
Radiated and Conducted Emissions
EN50081-2 Class A
Electrical /EMC
The module has passed testing at the following levels.
ESD Immunity (IEC1000-4-2)
4 kV contact, 8 kV air, 4 kV indirect
Radiated Immunity (IEC1000-4-3)
10V/m, 80…1000 MHz, 80% amplitude
Fast Transient Burst (IEC1000-4-4)
2 kV, 5 kHz
Surge Immunity (IEC1000-4-5)
2 kV common mode, 1 kV differential mode
Conducted Immunity (IEC1000-4-6)
10V, 0.15…80 MHz
(1)
(1)
Conducted Immunity frequency range may be 150 kHz…30 MHz if the radiated immunity frequency range is
30…1000 MHz.