beautypg.com

Rockwell Automation 1769-BOOLEAN Compact I/O Module Reference Manual User Manual

Page 67

background image

Publication 1769-RM016A-EN-P - July 2006

1769-BOOLEAN Module Specifications 67

Output Specifications

Environmental Specifications

Attribute

Value

Voltage Category

24V dc

Operating Voltage Range

20.4…26.4V dc (source

(3)

)

(3)

Sourcing Output - Source describes the current flow between the I/O module and the field device. Sourcing output circuits
supply source current to sinking field devices. Field devices connected to the negative side (dc common) of the field power
supply are sinking field devices. Europe: DC sinking input and sourcing output module circuits are the commonly used options.

Number of Outputs

4

Signal Delay, Max (resistive load)

Turn-on: 10 µs, output on-state current > 5 mA
Turn-off: 10 µs, output on-state current > 5 mA

Off-state Leakage, Max

(1)

(1)

Typical Loading Resistor - To limit the effects of leakage current through solid state outputs, a loading resistor can be
connected in parallel with your load. Use a 5.6 kohm, 1/2 W resistor for transistor outputs, 24V dc operation.

1.0 mA @ 26.4V dc

On-state Current, Min

1.0 mA

On-state Voltage Drop, Max

1.0V dc @ 1.0 A

Continuous Current per Point, Max

0.5 A @ 60 °C (140 °F)
1.0 A @ 30 °C (86 °F)
Refer to Temperature Derating.

Surge Current, Max

(2)

(2)

Recommended Surge Suppression - Use a 1N4004 diode reverse-wired across the load for transistor outputs switching 24V dc
inductive loads. For additional details, Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley publication
1770-4.1.

2.0 A (Repeatability is once every 2 s for a duration of
10 ms.)

Output Point to Bus (CompactBus) Isolation

Verified by one of the following dielectric tests: 1200V
ac for 1 s or 1697V dc for 1 s
75V dc working voltage (IEC Class 2 reinforced
insulation)

Attribute

Value

Storage Temperature

-40…85 °C (-40…185°F)

Operating Temperature

0…60 °C (32…140 °F)

Operating Humidity

5…95% noncondensing

Operating Altitude

2000 m (6561 ft)

Vibration, Operating

10…500 Hz, 5 g, 0.030 in. max peak-to-peak

Shock, Operating

Shock, Nonoperating

30 g panel mounted (20 g DIN-rail mounted)

40 g panel mounted (30 g DIN-rail mounted)

Radiated and Conducted Emissions

EN50081-2 Class A

Electrical /EMC

The module has passed testing at the following levels.

ESD Immunity (IEC1000-4-2)

4 kV contact, 8 kV air, 4 kV indirect

Radiated Immunity (IEC1000-4-3)

10V/m, 80…1000 MHz, 80% amplitude

Fast Transient Burst (IEC1000-4-4)

2 kV, 5 kHz

Surge Immunity (IEC1000-4-5)

2 kV common mode, 1 kV differential mode

Conducted Immunity (IEC1000-4-6)

10V, 0.15…80 MHz

(1)

(1)

Conducted Immunity frequency range may be 150 kHz…30 MHz if the radiated immunity frequency range is
30…1000 MHz.

This manual is related to the following products: