Error codes – Rockwell Automation 1769-BOOLEAN Compact I/O Module Reference Manual User Manual
Page 62
![background image](/manuals/579366/62/background.png)
Publication 1769-RM016A-EN-P - July 2006
62 Module Diagnostics and Troubleshooting
Error Codes
Error codes can help troubleshoot your module.
1769-BOOLEAN Module Extended Error Codes
Error Type
Hex
Equivalent
(1)
Module
Error Code
Extended Error
Information
Code
Error Description
Binary
Binary
No Error
X000
000
0 0000 0000
No Error
General Common
Hardware Error
X200
001
0 0000 0000
General hardware error; no additional information
X201
001
0 0000 0001
Power-up reset state
Hardware Specific
Error
X300
001
0 1000 0000
General hardware error
X301
001
0 1000 0001
Microprocessor hardware error
X302
001
1 0000 0010
ASIC hardware error
Configuration
Error
X400
010
0 0000 0000
General configuration error; no additional
information
X401
010
0 0000 0001
Invalid output interrupt enable, OUT0
(3)
X402
010
0 0000 0010
Invalid output interrupt enable, OUT1
X403
010
0 0000 0011
Invalid output interrupt enable, OUT2
X404
010
0 0000 0100
Invalid output interrupt enable, OUT3
X405
010
0 0000 0101
Invalid Operand_A, OUT0
(4)
X406
010
0 0000 0110
Invalid Operand_A, OUT1
X407
010
0 0000 0111
Invalid Operand_A, OUT2
X408
010
0 0000 1000
Invalid Operand_A, OUT3