Operand_a, out1, Operand_a, out2, Operand_a, out3 – Rockwell Automation 1769-BOOLEAN Compact I/O Module Reference Manual User Manual
Page 63
Publication 1769-RM016A-EN-P - July 2006
Module Diagnostics and Troubleshooting 63
Error Type
Hex
Equivalent
(2)
Module
Error Code
Extended Error
Information
Code
Error Description
Binary
Binary
X409
010
0 0000 1001
X40A
010
0 0000 1010
X40B
010
0 0000 1011
X40C
010
0 0000 1100
X40D
010
0 0000 1101
Invalid Operand_C OUT 0
X40E
010
0 0000 1110
X40F
010
0 0000 1111
X410
010
0 0001 0000
X411
010
0 0001 0001
Invalid Boolean expression, OUT 0
(5)
X412
010
0 0001 0010
Invalid Boolean expression, OUT 1
X413
010
0 0001 0011
Invalid Boolean expression, OUT 2
X414
010
0 0001 0100
Invalid Boolean expression, OUT 3
X415
010
0 0001 0101
Invalid Output Delay value, OUT 0
(6)
X416
010
0 0001 0110
Invalid Output Delay value, OUT 1
X417
010
0 0001 0111
Invalid Output Delay value, OUT 2
X418
010
0 0001 1000
Invalid Output Delay value, OUT 3
X419
010
0 0001 1001
Invalid Output Duration value, OUT 0
(7)
X41A
010
0 0001 1010
Invalid Output Duration value, OUT 1
X41B
010
0 0001 1011
Invalid Output Duration value, OUT 2
X41C
010
0 0001 1100
Invalid Output Duration value, OUT 3
(1)
X represents the Don't Care digit.
(2)
X represents the Don't Care digit.
(3)
EI_O bit set (1) while DB bit set (1).
(4)
Operand value not between 0 and 32 decimal.
(5)
Invalid Boolean expression configuration. Refer to Boolean Expression Configuration Restrictions on page 15, for valid Boolean expression configurations.
(6)
Output Delay value less than 0 or greater than 1000 decimal.
(7)
Output Duration value less than 0 or greater than 1000 decimal.