Programming Techniques
Chapter 5
5-9
Another approach for reducing the amount of data transferred across a
backup communication channel is to use Data Highway or Data Highway
Plus communication. Although you will still need a backup communication
channel to provide protection against having both processors controlling
outputs at the same time, you can use a Data Highway or Data Highway
Plus port as an additional backup communication channel.
For further information about using communication adapter modules, refer
to the 1775-KA Communication Adapter Module User’s Manual
(publication 1775-6.5.1) and the 1775-S5, -SR5 I/O Scanner
Communication Adapter Module User’s Manual (publication 1775-6.5.5).
The data table status section of PLC-3 memory contains information about
PLC-3 operation. Table 5.A lists the status information for the backup
system configuration.
Table 5.A
Data Table Status
Status Information
File
Word
Bit
Run/Backup Bit
S0
3
17
BackedĆup/notĆbackedĆup Bit
S0
3
16
Communication Error Bit
S0
2
10
Program Checksum
S0
4 & 5
-
1775ĆMX Module Communication
S4
0
-
1775ĆMX Module Program Compare
S4
1 & 2
-
1775ĆMX Module System ID
S4
3
-
1775ĆMX Module Backup to Primary
Transfer Data Words
S4
4 - 19
-
Run/Backup Bit
The run/backup bit (file 0, word 3, bit 17) indicates whether or not the
processor is acting as a backup processor. This bit is set in the primary
processor and reset in the backup processor.
Using Data Table Status Bits