Installing a Backup System

Chapter 2

2-10

Figure 2.7

Location of Backup Switches for 1775ĆS5 and 1775ĆSR5 Scanner

Modules

18754

Backup Switch at

Bottom Edge of Module

Terminator Switch at

Bottom Edge of Module

Figure 2.8

Setting Backup Switches on 1775ĆS5 and 1775ĆSR5 Scanner Modules

1

2

3

4

Switch Positions:

UP = Switch is away from board

DOWN = Switch is toward board

Not Used

(always UP)

Not Used

(always UP)

Set per

Table 2.B

ON

OFF

ON

OFF

OFF

ON

10975ĆI

Table 2.B

Backup Switches for 1775ĆS5 and 1775ĆSR5 Scanner Modules

Switch

Switchover Method 2

3

Processor

Automatic switchover with controllable

switchback

DOWN

UP

both primary and backup

Automatic switchover with no

switchback

DOWN

UP

UP

UP

primary

backup

Manual switchover

UP

DOWN

both primary and backup

StandĆalone mode

UP

UP