Installation
Chapter 3
3-7
Selecting the Network Link
You use Switch Assembly SW-7, a spare assembly in all Series A
modules, to select whether the KF2 treats the network link as a Data
Highway or as a PCL.
The following table shows the settings for Switch Assembly SW-7:
For This Network:
Set Switch 1: Set Switch 2:
Data Highway
OFF
OFF
Peer Communication Link
ON
OFF
Selection of RS-232-C/RS-422-A
Switch Assembly SW-8 lets you select whether the asynchronous
interface uses RS-232-C or RS-422-A standard communication.
For Communication Using Standard:
Set Switch 1: Set Switch 2:
RS-232-C
OFF
ON
RS-422-A
ON
OFF
Important: This is the only option switch that affects KF2 operation
after power-up. It changes the voltage applied to the network link
connector pins to those required for the standard selected. Set this switch
BEFORE power-up.
Replacing a 1771-KD Module with a KF2 Module
By setting the switches properly on the KF2 module, you can use it to
replace an older 1771-KD module in an existing application without
having to make any changes in your application programs.
In Set
Switch Ass’y
Switch
No.
Setting
SW-1
1
OFF
2
Same Setting as 1771-KD Switch (Assembly SW-1, Switch 1)
3
OFF
4
OFF
5
OFF
SW-2
1, 2
Same Setting as 1771-KD Switches (Assembly SW-2, Switches 1 and 2)
SW-3
1, 2, 3
Same Setting as 1771-KD Switches (Assembly SW-3, Switches 1, 2, and 3)
SW-4
1, 2, 3
Same Setting as 1771-KD Switches (Assembly SW-4, Switches 1, 2, and 3)
SW-5
1, 2
Same Setting as 1771-KD Switches (Assembly SW-5, Switches 1 and 2)
SW-6
1, 2, 3
Same Setting as 1771-KD Switches (Assembly SW-6, Switches 1, 2, and 3)
4
Same Setting as 1771-KD Switch (Assembly SW-1, Switch 5)
SW-7
1, 2
OFF
SW-8
1
OFF
2
ON