Appendix C
EtherNet/IP IO Data Mapping
Produced (Input) Assembly
(Instance 0x66)
Instance 0x66 describes another input (produced) assembly for the 1609-UPS.
Instance 0x66 – Produced (Input) Assembly
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Reserved for Logix (Logix sets to 0xffff whenever the connection is not established. UPS sets to 0x0000.)
1
2
3
4
Reserved UPSShutDown OutputOff
UPSOff
Output
Source
Boosting
Output
Source
Reducing
Output
Source
Battery
Output
Source
Normal
5
Reserved
AC Failed
Battery
Depleted
AC Failed
BatteryLow
AC Failed
Battery OK
AC Normal
Battery
Replace
AC Normal
Battery
Weak
AC Normal
Battery
Good
6
Battery
Discharging
Battery
Resting
Battery
Charging
Battery
Floating
7
OutputBad
OverTemper
ature
OutputOver
Load
Load
Warning
Power Fail
8
Smart
Shutdown
Disconnect
InverterAbn
ormal
FanFail
ChargerFail
9
Battery Deep
Test Fail
Battery Test
Fail
General Test
Fail
Test
Passed
Test In
Progress
10
OutputVoltage (low byte)
11
OutputVoltage (high Byte)
12
OutputCurrent (low byte)
13
OutputCurrent (high byte)
14
OutputPower (low byte)
15
OutputPower (high byte)
16
OutputLoad (low byte)
17
OutputLoad (high byte)
18
OutputFrequency (low byte)
19
OutputFrequency (high byte)
20
BatteryVoltage (low byte)
21
BatteryVoltage (high byte)
22
BatteryCapacity (low byte)
23
BatteryCapacity (high byte)
24
BatteryEstimatedTime (low byte)
25
BatteryEstimatedTime (high byte)
26
BatteryTemperature (low byte)
27
BatteryTemperature (high byte)