Rockwell Automation 1609-ENET Ethernet Network Card Quick Start User Manual
Page 27

Rockwell Automation Publication 1609-QS002A-EN-P - May 2014
27
Appendix B
EtherNet/IP Parameters
19
Required
Get
V
Input Line Value
STRUCT of:
The current input values for up to InputNumLines
Frequency
INT
Line frequency to the UPS system in
1/10 Hz
Voltage 1
INT
Line voltage of the UPS system in
1/10 V
20
Required
Get
V
OutputSource
INT
The present source of output power. The
enumeration none(7) indicates that there is no
source of output power (and therefore no output
power), for example, the system has opened the
output breaker
normal(0),
battery(1),
bypass(2),
reducing(3),
boosting(4),
manualBypass(5),
other(6),
none(7)
21
Required
Get
V
OutputFrequency
INT
The present output frequency in
1/10 Hz
22
Required
Get
V
OutputNumLines
INT
The number of output lines utilized in this device
23
Required
Get
V
Output Line Status
Array of
STRUCT of:
The Output Line values for up to OutputNumLines
Voltage
INT
line voltage of the UPS system in
1/10V
Current
INT
line current of the UPS system in
1/10 A
Power
INT
line eal power of the UPS system in watts
Load
INT
line load expressed in percent of rated capacity
24
Required
Get
V
BatteryCondition
INT
The indication of the capacity remaining in the
UPS system's batteries when AC normal.
good(0),
weak(1),
replace(2)
25
Required
Get
V
BatteryStatus
INT
The indication of the capacity remaining in the
UPS system's batteries when AC failed. A value
of ok indicates that the remaining run-time is
greater than upsConfigLowBattTime. A value of
low indicates that the remaining battery run-time
is less than or equal to upsConfigLowBattTime.
A value of depleted indicates that the UPS will be
unable to sustain the present load when and if the
utility power is lost (including the possibility that
the utility power is currently absent and the UPS is
unable to sustain the output).
ok(0),
low(1),
depleted(2)
26
Required
Get
V
BatteryCharge
INT
floating(0),
charging(1),
resting(2),
discharging(3)
27
Required
Get
V
BatteryEstimatedTime
INT
Estimated time from backup to low battery
shutdown
28
Required
Get
V
BatteryVoltage
INT
The magnitude of the present battery voltage in
1/10 V
29
Required
Get
V
BatteryCapacity
INT
An estimate of the battery charge remaining
expressed as a percent of full charge
30
Required
Get
V
Battery Temperature
INT
The ambient temperature at or near the UPS
Battery casing
°C
31
Required
Get/Set
V
TestType
INT
Perform the UPS Test procedure
abort(0),
generalTest(1),
batteryTest(2),
testFor10sec(3),
testUntilBattlow(4)
UPS Object (0x377)
Attribute ID Need
Access Rule
NV
Name
Data Type
Description of Attribute
Semantics of value