Appendix C
EtherNet/IP IO Data Mapping
Appendix C - EtherNet/IP IO Data Mapping
If you want to control the UPS device just over the UDP (I/O Connection)
Interface, it is sufficient to use the mapping described. This section describes
the mapping. The different mappings over different instances are selected
in the assembly class.
Configuration Assembly
(Instance 0x64)
Consumed (Output) Assembly
(Instance 0x65)
Instance 0x64 – Configure Assembly (14 Bytes)
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Configuration Revision Number
1
Sensitivity
High Bit
Sensitivity
Low Bit
Buzzer
Enable
AutoReboot
2
Low Voltage Transfer Point (low byte)
3
Low Voltage Transfer Point (high byte)
4
High Voltage Transfer Point (low byte)
5
High Voltage Transfer Point (high byte)
6
Shutdown Delay (low byte)
7
Shutdown Delay (high byte)
8
Boot Delay (low byte)
9
Boot Delay (high byte)
10
External Battery Pack (low byte)
11
External Battery Pack (high byte)
Instance 0x65 –Consumed (Output) Assembly
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Restart Bit
ShutDown Bit
SilenceAlarm
1
Perform Test Procedure
2
Shutdown Seconds (low byte)
3
Shutdown Seconds (high Byte)
4
Restart Seconds (low byte)
5
Restart Seconds (high byte)