Rockwell Automation 1609-ENET Ethernet Network Card Quick Start User Manual
Page 26

26
Rockwell Automation Publication 1609-QS002A-EN-P - May 2014
Appendix B
EtherNet/IP Parameters
UPS Object (0x377)
Attribute ID Need
Access Rule
NV
Name
Data Type
Description of Attribute
Semantics of value
1
Required
Get
NV
Output Rating
STRUCT of:
The magnitude of the nominal output
NV
VA
INT
VA rating
NV
Voltage
INT
Voltage rating
NV
Frequency
INT
Frequency rating
2
Required
Get
NV
Input Rating
STRUCT of:
The magnitude of the nominal input
NV
Voltage
INT
Voltage rating
NV
Frequency
INT
Frequency rating
3
Required
Get
NV
RatingBatteryVoltage
INT
The magnitude of the nominal battery
voltage rating
4
Required
Get
NV
LowTransferVoltage
STRUCT of:
The Setup of low line input voltage that allowed
the UPS system transfers to the battery source
NV
UpBound
INT
The maximum voltage limited for the
LowTransferVoltage
NV
LowBound
INT
The minimum voltage limited for the
LowTransferVoltage
5
Get
NV
HighTransferVoltage
Array of
STRUCT of:
The Setup of high line input voltage that allowed
the UPS system transfers to the battery source
NV
UpBound
INT
The maximum voltage limited for the
HighTransferVoltage
NV
LowBound
INT
The minimum voltage limited for the
HighTransferVoltage
6
Required
Get
NV
UPS Type
INT
Indicate the UPS type
on-line(1)
off-line(2),
line-interactive(3),
three-phase(4),
splite-phase(5)
All other values
reserved
7
Required
Get/Set
NV
AutoReboot
INT
In backup mode, the UPS may shutdown normally
by SDA command, dry-contact remote shutdown
signal or low battery shutdown. This command is
used to determine the unit should restart or not
next time when the power restores
on(1),
off(2)
All other values
reserved
8
Required
Get/Set
V
ShutdownAction
INT
If the value is greater than 0 the UPS performs
shutdown action that defined by ShutdownType
after the seconds. 0, aborted
9
Required
Get/Set
V
RestartAction
INT
UPS will restart after the indicated number
of minutes.
-1, aborted
10
Required
Get/Set
NV
BuzzerAlarm
UINT
UPS will keep silence but will alarm again when
next power event is occurred
alarm(1),
silence(2)
11
Required
Get/Set
NV
BuzzerState
INT
If it is disabled then the UPS is always muted
enable(1),
disable(2)
12
Required
Get/Set
NV
Sensitivity
INT
The sensitivity of the UPS to utility line
abnormalities or noises
normal(0),
reduced(1),
low(2)
13
Required
Get/Set
NV
LowVoltageTransferPoint
INT
The input minimum line voltage allowed before
the UPS system transfers to battery backup
14
Required
Get/Set
NV
HighVoltageTransferPoint
INT
The input maximum line voltage allowed before
the UPS system transfers to battery backup
15
Required
Get/Set
V
ShutdownOSDelay
INT
The operating system shutdown delay time when
the input power fail
16
Required
Get/Set
NV
UPSBootDelay
UINT
Delay the UPS startup after power restores.
The power quality may not stable when power
restores, this feature let the UPS wait a period
of time to startup the system
17
Required
Get/Set
NV
ExternalBatteryPack
INT
Indicate the number of external battery pack
18
Required
Get
V
InputNumLines
INT
The number of input lines utilized in this device
Limited 1