Powermonitor 3000 13

Table 10 DeviceNet Optional Communications (catalog numbers ending in -DNT)

LED

LED Color

LED State and Communications
Condition

F1

Off

Not Used

F2

Off

Not Used

NETWORK STATUS

Off

Power is off or the Powermonitor 3000 is
not online

Flashing Green

Network status is OK, no connections
established

Steady Green

Network status is OK, connections
established

Flashing Red

Recoverable communications failure; port is
restarting

Steady Red

Non-recoverable communications error;
check wiring and configuration parameters

Table 11 Ethernet Optional Communications (Series A catalog numbers ending in
-ENT)

LED

LED Color

LED State and Communications
Condition

LINK

Off

Ethernet connection is inactive

Steady Green

Ethernet connection is active

RX

Off

Ethernet is idle, no active data present on
port

Flashing Red

Active data is present on Ethernet port

TX

Off

Powermonitor 3000 is not transmitting any
data through the Ethernet port

Flashing Red

Powermonitor 3000 is transmitting data

Powermonitor 3000

F1

F2

NETWORK
STATUS

Powermonitor 3000

LINK

RX

TX