Step 7 - Wire the Control Signal Terminal Block
1329I-5.5 Integrated Drive/Motor — January, 2000
7.3
Wiring the Relay Control Output
A single form A relay on the terminal block can be used to indicate the unit is running
(default) or has faulted (user option) based on the setup DIP switch setting. Refer to the
setup DIP switch description in Chapter 8.
Figure 7.6
Relay Control Output Wiring
7.4
Wiring RPM or Percent Load Display
The RPM or Percent Load Display input (control terminal 12) selects the type of
information displayed by the analog output and the built-in display, speed in RPM or
percent load. Wire a switch between control terminals 12 and 13 as shown in Figure 7.7.
Figure 7.7
RPM or Percent Load Display Wiring
7.5
Wiring the Speed Reference
The standard 1329I unit provides two motor speed reference options:
• Seven preset speeds
• An external 0 to 10 VDC or 4 to 20 mA speed reference source
The 1329I unit with local provides three motor speed reference options:
• The local operator controls (using the
keys)
• Seven preset speeds (the
keys are not used)
• An external 0 to 10 VDC or 4 to 20 mA speed reference source (the
keys
are not used)
17
18
19
20
N.O. Relay
Relay Common
Connect to external device
such as PLC input.
11
12
13
14
RPM or Percent Load Display
24V DC
RPM
% Load